Skip to main content
Waters

How to install EZinfo - WKB234827

Article number: 234827

OBJECTIVE or GOAL

Install EZinfo.

ENVIRONMENT

  • EZinfo
  • waters_connect/UNIFI
  • UNIFI
  • MassLynx

PROCEDURE

  1. On the workstation, PC, or client (in a waters_connect server environment), double-click on the installer, or right-click and select Install (shown below). Note that there is no "run as administrator" option, so you must run it from a user account with admin rights.
    clipboard_e8e8a8d79cbb5bfae20ad7b333d7779c0.png

  2. Select "Next" in the Setup Wizard.
    clipboard_e43b42b88dd55d4aefae8f21de284aab1.png

  3. Accept Terms and Conditions and select Next.
    clipboard_ec3846e8e6cf35d7aca25e169b59a8fa0.png

  4. Next is the option to change the default installation location. Typically, the default settings are used and Next is selected. If a custom installation location is needed, select the browse option.
    clipboard_e0ba6cb5897fc295c49a90d723fbd08ed.png

  5. Select Install.
    clipboard_eb3c3c36a74fa7b928739649729f0a6b6.png

  6. Wait for the installer to run.
    clipboard_eccc211775ef269cb333206b0668caed4.png

  7. Click Finish.
    clipboard_e258f6ca97e52ad5a5b3f074ac70166fa.png

  8. You can access EZinfo from the startup menu or from within waters_connect or Progenesis QI (depending on what else is installed on the PC).
    clipboard_e309799242dd5bf42a060c66f9b6688e7.png

ADDITIONAL INFORMATION

Not able to find a solution? Click here to request help.