No fibre optic communications and Beam Control Unit has no power on the AutoSpec - WKB48735
SYMPTOMS
- MassLynx very slow to boot. - Several minutes.
- Error message shown when MassLynx has eventually started.
- Error processing file C:\MassLynx\AutospecVXWORKS\ASPECVAC.INI/error reading line 0x0 /rioPropertyGetInstanceID:Null handle/
- No Instrument control.
ENVIRONMENT
- AutoSpec Premier (P)
- AutoSpec Ultima (M)
- MassLynx
CAUSE
Fault in instrument internal Fibre Optic Loop communications. Beam Control Unit off with no power.
FIX or WORKAROUND
- Close MassLynx.
- Lock the system into "Standby" using the front panel Instrument Status Switch.
- Reboot the EPC and monitor boot progress by typing " PING EPC -t" into the Start/Run box.
- A command Box will open and show ping responses during the boot.

- Wait up to 2 minutes until many responses show less than 1ms to reply. - Indicates boot sequence has completed.
- Close the Ping window.
- Run rioMainMenu to check the status of the instrument internal loop communications:
- Enter "TELNET EPC" into the Start/Run box.
- Telnet will open with a "->" prompt.
- Enter "rmm" followed by return into the Telnet window. - All characters should be entered in lower case.
- The following will be displayed:
***********************************
*
* RIO Main Menu
*
***********************************1. Shutdown RIO
2. Set Menu Size
3. Access subsystems
4. Lock All subsystems
5. Unlock All subsystems
6. Start Memory-Mapped Page Poll
7. Stop Memory-Mapped Page Poll
999. EXITchoice>
- Enter "3" into "choice" to display which units are present on the Instrument Internal Loop communications path.
- the following will be displayed:
choice> 3
***********************************
*
* Available subsystems
*
***********************************4. MA3481-200 Source Unit
6. MA3606 Source Unit
7. MA3779-200 PCI Card
999. EXITchoice>
- The above list of 3 "Subsystems" confirms a failure in the internal loop communications path.
- Enter "999" two or three times until the "->" is displayed.
- Close the Telnet Window
-
Remove the panel to expose the Beam Control Unit. This is located at the front of the instrument underneath the Magnet. - See the location diagram in additional information.
- Check that the "Standby" power switch on the front of the Beam Control Unit is illuminated.
- If no illumination is seen check FS1.
- Power off the Beam Control Unit "Standby" Power switch. Set it to position "0".
- Power off the "Bench" Circuit Breaker located on the Mains Distribution Unit located at the front of the instrument underneath the GC
- See the location diagram in additional information.
- Remove FS1 with the aid of a small coin or large slotted screwdriver.
- Check the fuse for visible burning or with the aid of a Digital Volt Meter.
- Open Circuit, infinite or very high resistance, would indicate a failed fuse.
- Replace the fuse with the identical item. PN 1340141-S FUSE GLASS 1.25A 20MM A/S (10/PACK)
- Power on the "Bench" Circuit Breaker
- Set the Beam Control Unit "Standby" Switch to the On, "1" position.
- Check for illumination in the "Standby" switch.
- Note the "Operate" Switch will not show any illumination
- Check power cable for 240V AC. If no power check the power strip located underneath Magnet that 240 V AC is being supplied to it
- If Yes check fuse within strip
- If No check FS3 in AC Distribution unit.
- Restart the EPC and as above monitor the boot progress via "PIN EPC -t" closing the window when complete.
- Run rioMainMenu to recheck the status of the instrument internal loop communications:
- Enter "TELNET EPC" into the Start/Run box.
- Telnet will open with a "->" prompt.
- Enter "rmm" followed by return into the Telnet window. - All characters should be entered in lower case.
- The following will be displayed:
***********************************
*
* RIO Main Menu
*
***********************************1. Shutdown RIO
2. Set Menu Size
3. Access subsystems
4. Lock All subsystems
5. Unlock All subsystems
6. Start Memory-Mapped Page Poll
7. Stop Memory-Mapped Page Poll
999. EXITchoice>
- Enter "3" into "choice" to check which units are present on the Instrument Internal Loop communications path.
- The following will be displayed:
choice> 3
***********************************
*
* Available subsystems
*
***********************************1. MA3445 Beam Unit
2. MA3458 Heater Unit
3. MA3481-201 Source Unit
4. MA3481-200 Source Unit
5. MA3515 Vacuum Unit
6. MA3606 Source Unit
7. MA3779-200 PCI Card
999. EXITchoice>
- The above list of 7 "Subsystems" present confirms good internal loop communications.
- Enter "999" two or three times until the "->" is displayed.
- Close the Telnet Window
- Start MassLynx which will boot normally.
- Refit any removed instrument panels.
- Check in the tuning window the Solenoid Slit Settings if applicable. - These may have set to default values. Re-enter the values from a saved copy.
- Restart the Magnet.
- The system will now be fully operational. The Instrument Status switch may be set to Operate to allow the instrument to be set into operate.
ADDITIONAL INFORMATION

