Skip to main content
Waters

Alliance pressure fluctuation or no flow - WKB7030

Article number: 7030

SYMPTOMS

  • Pressure fluctuations observed after changing mobile phase
    • Pressure fluctuations between 100 psi and 700 psi at 0.3 mL/min in 100% water
  • Several wet prime cycles, no air bubbles
  • V3 purge outlet clear waste line does not have a steady stream of flow during prime
  • Water in line A and B
  • Acetonitrile in lines C and D
  • Early retention times

ENVIRONMENT

  • 2695 Separations Module
  • 2795 Separations Module

CAUSE

Air bubbles in lines, loss of prime in solvent manager.

FIX or WORKAROUND

Priming the solvent manager:

  1. Perform a manual dry prime using a syringe to draw mobile phase from each line.
  2. Perform a wet prime on each solvent management mobile phase line.
  3. Operate flow rate and confirm pressure stability.
  4. If pressure fluctuations continue:
    • Repeat steps using methanol to remove all air in the lines.
    • Consider wet priming one additional step using 25%A, 25%B, 25%C, 25%D composition each line.

ADDITIONAL INFORMATION

For more information, refer to the Waters Alliance e2695 Separations Module Operators Guide.

id7030, 2690, 2690D, 2690DUPGD, 2690UP, 2695, 2695D, 2695DE, 2695DEB, 2695DUP, 2695E, 2695EB, 2695INERT, 2695UP, 2790XE, 2790XEUP, 2795E, 2795UP, 2795XE, A-10SSM, ALLCOLCLR, ALLCOLHTR, ALLCOLHTRB, Delta, eluent, pressure ripple

Not able to find a solution? Click here to request help.