Column Manager "column door open while running" message - WKB622
Article number: 622
SYMPTOMS
- Sample Manager produces an error message "column x door open while running" and stops the run.
- Active preheater does not achieve the programmed set point temperature for the selected column
ENVIRONMENT
- ACQUITY UPLC H-Class Column Manager-Active
- ACQUITY UPLC I-Class Column Manager-Active
- ACQUITY APC Column Manager-Single Zone
CAUSE
1. The magnet on the internal cover is missing.
2. The door is broken not giving enough contact for the magnet sensor to work.
FIX or WORKAROUND
- Replace the magnet or replace column trough cover assembly.
- Part number 410003267 for the magnet
- Part number 700005439 for the Column Module Front Trough Cover
- Part number is 700009538 for the Column Module Cover for the CM-S
ADDITIONAL INFORMATION
- The magnet is located on the column trough cover. The read sensor is located within the dual column trough assembly.
- Closing the compartment trough cover engages a magnet switch that turns on the 24V to the active preheater.
- The active preheater operates at the set point temperature of the selected column position when the trough compartment cover is closed.
id622, APH, UPASMFTN, UPIBSM, UPIBSM+, UPISMFL, UPISMFL+, UPISMFTIVD, UPISMFTN, UPISMFTN+, UPQSM, UPQSM+, UPQSMBIO, UPQSMBIO+, UPSMFTN, UPSMFTN+, UPSMFTNB+, UPSMFTNBIO