Skip to main content
Waters

How to connect an external Solvent Select Valve (SSV) to a Solvent Manager - WKB27360

Article number: 27360

ENVIRONMENT

  • ACQUITY UPLC Binary Solvent Manager (BSM)
  • ACQUITY UPLC I-Class
  • ACQUITY UPLC H-Class

ANSWER

Event 4 is always on (or closed) for all external valve positions. Hard wire the valve connection that should be connected to event 4 directly to ground. This will mimic the event being on all the time, which is required for all valve positions.

ADDITIONAL INFORMATION

  • SSV Event Switch Connections on an I-Class BSM. Note that the rear connection ports may differ between different solvent manager variants.
  • The Solvent Selection Valve may also be installed on the Sample Manager.
  • The Solvent Selection Valve must be configured in the method. See the table below for configuration schemes.
    clipboard_e8b39391da73b57522d271931bc43505d.png

UPBINARY, UPBSM+, UPIBSM, UPIBSM, UPIBSM+, UPIBSM+, UPISMFL, UPISMFL+, UPISMFTIVD, UPISMFTN, UPISMFTN+, UPPBSM, UPQSM, UPQSM+, UPQSMBIO, UPQSMBIO+, UPSMFTN, UPSMFTN+, UPSMFTNB+, UPSMFTNBIO

Not able to find a solution? Click here to request help.